← Edition of Thursday 26 November 2026

Cold chain · flaw without a fix

Cold chain: an unpatched Danfoss flaw, three older ones in CISA's exploited catalogue, UK supermarkets unplug their fridges

Reading time: 3 min · 7 sources
KEY POINTS

Danfoss AK-SM 800A controllers, found in supermarkets and cold rooms across Europe, combine a critical flaw without a fix and three flaws whose exploitation CISA now confirms. After the October and November attacks, the topic belongs to operations management as much as to IT.

The facts

CISA warns of CVE-2026-129713, a memory overflow in the server of the AK-SM 820A, 850A and 880A controllers, rated 9.8 and triggerable without authentication: it causes a restart and can lead to code execution with the web server's rights. No fix exists; the Danfoss advisory of 20 November announces one in a future 5.5.x release, which will also remove the option to disable strict mode. The Hacker News reports six further flaws without identifiers, reported by researchers and Germany's BSI, affecting 5.3.2 and earlier.

No source establishes that CVE-2026-129713 was used in the attacks. The flaws with confirmed exploitation are the three added to CISA's catalogue on 25 November: CVE-2025-41450 (improper authentication, due 9 December), CVE-2023-25914 (path traversal) and CVE-2023-25915 (input validation), due 28 November. The latter two have been known since 2023.

The cold-chain attacks hit French supermarkets on 11 and 12 October (attributed to the IRGC-linked Shahid Kaveh unit, defrost settings altered on Danfoss and Copeland controllers), then at least 115 shops in Belgium, the Netherlands, Sweden, Luxembourg, Ireland, Romania and Estonia in early November. ENISA and the European Commission issued a joint statement on 4 November.

In the UK, Risky Business reports from the BBC a campaign coordinated by authorities and researchers to take thousands of supermarket fridges and freezers offline, with the major chains mobilising their IT teams. This is a secondary source; no NCSC statement has been seen.

Why it matters

These controllers set the temperature of refrigerated cabinets, cold rooms and sometimes pharmaceutical warehouses. One altered setting over a night destroys stock, triggers a product recall or spoils vaccines and medicines. The October attacks showed that the goal was damage, not ransom.

The equipment usually sits outside IT's view: installed by a refrigeration contractor, connected through a 4G modem or a dedicated router for remote maintenance, protected by default passwords. It appears in no IT inventory and is covered by no security monitoring. CISA adding three-year-old flaws to its exploited catalogue says a lot about the state of the installed base.

Taking the devices off the internet, as the UK is doing, is the simplest answer when no fix exists: remote maintenance can run through a controlled remote-access path rather than direct exposure. It is an organisational decision between operations, the maintenance contractor and IT.

What to decide

1Inventory: ask facilities management and maintenance contractors for the list of refrigeration controllers and how each is connected to the internet.
2Exposure: have direct internet access cut, 4G modems included, and route remote maintenance through a controlled remote-access path.
3Configuration: have strict mode enabled, default passwords changed, and setpoints and defrost cycles checked.
4Alerting: make sure a temperature drift raises an alert handled at night and at weekends, independently of the controller itself.

Timeline

11 OctAttacks on French supermarkets (11 and 12 October), defrost settings altered.
4 NovJoint ENISA and European Commission statement on cyber incidents in refrigeration systems.
20 NovDanfoss advisory: fix for CVE-2026-129713 announced for a future 5.5.x release.
25 NovCISA adds three AK-SM 800A flaws to its Known Exploited Vulnerabilities catalogue.
28 NovCISA deadline for CVE-2023-25914 and CVE-2023-25915; 9 December for CVE-2025-41450.